Skip to product information
1 of 1

DASHBUYS.COM

SCHNEIDER ELECTRIC LC1D123G7 CONTACTOR, 12A, 3P, 7.5HP, 480V - NEW OLD STOCK

SCHNEIDER ELECTRIC LC1D123G7 CONTACTOR, 12A, 3P, 7.5HP, 480V - NEW OLD STOCK

Regular price $199.99 USD
Regular price $378.01 USD Sale price $199.99 USD
Sale Sold out
Shipping calculated at checkout.
We currently have 1 in stock.

SCHNEIDER ELECTRIC LC1D123G7 CONTACTOR, 12A, 3P, 7.5HP, 480V - NEW OLD STOCK

IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

TeSys CONTACTOR
TeSys D ContactorNumber of Poles: 3-PolesPole Contact Composition: 3 NORated Operational Current: 12AControl Circuit Voltage: 120V AC 50/60 HzNon-Reversing
Product Specifications
[Icw] rated short-time withstand current 100 A - 1 s for signalling circuit
105 A 104 °F (40 °C) - 10 s for power circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
210 A 104 °F (40 °C) - 1 s for power circuit
30 A 104 °F (40 °C) - 10 min for power circuit
61 A 104 °F (40 °C) - 1 min for power circuit
[Ie] rated operational current 12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
16 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
16 A (at 140 °F (60 °C)) for power circuit
[Uc] control circuit voltage 120 V AC 50/60 Hz
[Ue] rated operational voltage Power circuit <= 300 V DC
Power circuit <= 690 V AC 25...400 Hz
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 2 for power circuit
40 A gG at <= 690 V coordination type 1 for power circuit
auxiliary contact composition 1 NO + 1 NC
auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
average impedance 2.5 mOhm - Ith 16 A 50 Hz for power circuit
Brand Schneider Electric
By Schneider Yes
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Carbon footprint (kg CO2 eq, Total Life cycle) 19
climatic withstand IACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heat
coil technology Without built-in suppressor module
Connections - Terminals Control circuit: spring terminals 1 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end
Control circuit: spring terminals 2 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end
Power circuit: spring terminals 1 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end
Power circuit: spring terminals 2 0.004 in² (2.5 mm²) - cable stiffness: flexible without cable end
contact compatibility M2
contactor application Motor control
Resistive load
control circuit type AC 50/60 Hz
control circuit voltage limits 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz
0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz
1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz
Depth 3.4 in (86 mm)
Device Short Name LC1D
Electrical Durability 0.8 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 12 A AC-3 <= 440 V
2 Mcycles 12 A AC-3e <= 440 V
Final Result for Flywheel performance tracking Non Flywheel
fire resistance 1562 °F (850 °C) IEC 60695-2-1
Flame Retardance V1 conforming to UL 94
Global Keywords 3-pole contactor
AC coil
AC-3
AC-3e
Built-in auxiliary contact
LC1D
Magnetic contactor
Motor control
Motor switching
Power contactor
Spring terminals
TeSys D
Heat Dissipation 2…3 W at 50/60 Hz
Height 3.9 in (99 mm)
Hold-In Power Consumption In Va 7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
inrush power in VA 70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
insulation resistance > 10 MOhm for signalling circuit
IP Degree of Protection IP20 front face IEC 60529
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A at 440 V for power circuit conforming to IEC 60947
250 A DC for signalling circuit conforming to IEC 60947-5-1
Manufacturer Schneider Electric
Maximum Horse Power Rating 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 575/600 V AC 50/60 Hz for 3 phase motors
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phase motors
3 hp at 230/240 V AC 50/60 Hz for 3 phase motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phase motors
maximum operating rate 3600 cyc/h 140 °F (60 °C)
3600 cyc/h at 60 °C
Mechanical Durability 15 Mcycles
Mechanical Robustness Shocks contactor closed 15 Gn for 11 ms)
Shocks contactor open 10 Gn for 11 ms)
Vibrations contactor closed 4 Gn, 5...300 Hz)
Vibrations contactor open 2 Gn, 5...300 Hz)
minimum switching current 5 mA for signalling circuit
minimum switching voltage 17 V for signalling circuit
motor power kW 3 kW at 220...230 V AC 50/60 Hz (AC-3)
3 kW at 220...230 V AC 50/60 Hz (AC-3e)
3.7 kW at 400 V AC 50/60 Hz (AC-4)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
5.5 kW at 415...440 V AC 50/60 Hz (AC-3)
5.5 kW at 415...440 V AC 50/60 Hz (AC-3e)
7.5 kW at 500 V AC 50/60 Hz (AC-3)
7.5 kW at 500 V AC 50/60 Hz (AC-3e)
7.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Mounting Support Plate
Rail
Net Weight 0.717 lb(US) (0.325 kg)
non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Operating Altitude 0...9842.52 ft (0...3000 m)
Operating Time 12...22 ms closing
4...19 ms opening
Overvoltage Category III
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Permissible Ambient Air Temperature Around The Dev 140…158 °F (60…70 °C) with derating
-40…140 °F (-40…60 °C)
pole contact composition 3 NO
Pollution Degree 3
power dissipation per pole 0.36 W AC-3
0.36 W AC-3e
1.56 W AC-1
Product Certifications CB Scheme
CCC
CSA
EAC
Marine
UKCA
UL
Product Or Component Type Contactor
protective cover With
Protective Treatment THIEC 60068-2-30
PVC free Yes
rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
REACh free of SVHC Yes
safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
signalling circuit frequency 25...400 Hz
Standards CSA C22.2 No 14
CSA C22.2 No 60947-4-1
EN 60947-4-1
EN 60947-5-1
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
IEC 60947-4-1
IEC 60947-5-1
UL 60335-2-40:Annex JJ
UL 60947-4-1
Sustainable packaging Yes
Take-back No
Toxic heavy metal free Yes
Type Of Network 3P
UNSPSC Classification v19 39121529
UNSPSC Classification v23 39121529
utilisation category AC-1
AC-3
AC-3e
AC-4
Width 1.8 in (45 mm)

 

CONDITION: UNIT IS NEW OLD STOCK. NEVER INSTALLED. UNIT HAS NO WARRANTY FROM DASHBUYS.COM AND SOLD AS-IS. BOX MAY HAVE MINOR STORAGE WEAR. MAIN PHOTO IS STOCK PHOTO ONLY. PLEASE ASK ANY QUESTIONS BEFORE PURCHASING.
SHIPPING: FREE UPS / USPS ON ALL ORDERS OVER $200
I:0842C43T

View full details